|
Categories
|
Information
|
Featured Product
|
|
|
 |
|
There are currently no product reviews.
 ;
Very good product. Best service manual. Many thanks
 ;
I am only search for 5 Minute, by it in 5 Minutes to and get ist in few ours! Best i found in the Internet and my Amplifer is repaired as well! Thank you
 ;
Readable text and good copy. Very much needed if you wish to do some repairs on this fine old unit.
 ;
Fint forløb med levering af manualen. Kvaliteten af skanningen betegnes som middel
 ;
I found the manual to be clear concise and complete. It was of immense assistance when removing the unit as the unit was over 22 years old and the wiring diagram was unobtainable from the manufacturer. The exploded drawings were clear as were the instructions and labels.
2. Flaring Work and Connection of Piping
1) Flaring work
Main cause for gas leakage is due to defect in flaring work. Carry out correct flaring work in the following procedure. 1. Cut the pipes and the cable. Use the piping kit accessory or the pipes purchased locally. Measure the distance between the indoor and the outdoor unit. Cut the pipes a little longer than measured distance. Cut the cable 1.5m longer than the pipe length.
Copper pipe 90° Slanted Uneven Rough
4. Flaring work Carry out flaring work using flaring tool as shown below. Outside diameter mm ø6.35 ø9.52 ø12.7 ø15.88 inch 1/4 3/8 1/2 5/8 A mm 0 ~ 0.5 0 ~ 0.5 0 ~ 0.5 0 ~ 1.0
Firmly hold copper pipe in a die in the dimension shown in the table above.
"A"
Handle Bar Bar Yoke Cone Copper pipe Clamp handle Red arrow mark
2. Burrs removal Completely remove all burrs from the cut cross section of pipe/tube. Put the end of the copper tube/pipe in a downward direction as you remove burrs in order to avoid dropping burrs into the tubing.
Pipe Reamer
5. Check
Point down
Compare the flared work with figure below. If flare is noted to be defective, cut off the flared section and do flaring work again.
3. Putting nut on Remove flare nuts attached to indoor and outdoor unit, then put them on pipe/tube having completed burr removal. (not possible to put them on after flaring work)
Flare nut Copper tube
Even length all round Inclined Surface Cracked Uneven damaged thickness Smooth all round Inside is shiny without scratches
= Improper flaring =
- 27 -
|
|
 |
> |
|
|
Parse Time: 0.21 - Number of Queries: 125 - Query Time: 0.048